LAW
Writer®
Ohio Laws and Rules
(A) If electrical power at a panoramic irradiator is lost for longer than ten seconds, the sources must automatically return to the shielded position.
(B) The lock on the door of the radiation room of a panoramic irradiator may not be deactivated by a power failure.
(C) During a power failure, the area of any irradiator where sources are located may be entered only when using an operable and calibrated radiation survey meter.
R.C.
119.032 review dates:
05/18/2012 and
05/15/2017
Promulgated
Under: 119.03
Statutory
Authority:
3748.04
Rule
Amplifies:
3748.04
Prior
Effective Dates: 10/20/2002