Skip to main content
Back To Top Top Back To Top
This website publishes administrative rules on their effective dates, as designated by the adopting state agencies, colleges, and universities.

Rule 3701-83-39 | Building and site requirements - freestanding birthing centers.

 

(A) Each freestanding birthing center shall provide sufficient space for the number of patients and patient families and staff members to assure privacy for patients and families including:

(1) A waiting room;

(2) An examination room;

(3) A staff area, conference area, or classroom; and

(4) A family room with a designated play area for children.

(B) Each center shall have a minimum of two birth rooms. The birth room shall:

(1) Be of adequate size and appropriate configuration to provide for the equipment, staff members, supplies and emergency procedures required for the physical and emotional care of the mother, family, and the newborn during birth, labor, and the postpartum period;

(2) Have a minimum floor area of one hundred and sixty square feet. The length or width of the room shall have a minimum dimension of eleven feet. The vestibule, toilet and bathing areas and closets will not be considered in determining the square footage;

(3) Have doorways and hallways of adequate width and configuration to accommodate the maneuvering of ambulance stretchers and beds;

(4) Be located to provide rapid unimpeded access to an exit of the building which can accommodate emergency transportation vehicles and the type and size of emergency equipment utilized for emergency transport; and

(5) Have hot and cold running water.

(C) Each center shall provide:

(1) Toilet and bathing facilities that include a toilet, sink, bath or shower facilities with appropriately placed grab bars for patients. The toilet and bathing facilities shall be shared by not more than two birth rooms;

(2) Toilet and hand washing facilities for families and personnel;

(3) Space for coats, boots, and umbrellas in inclement weather;

(4) A system of communication between the birth room and other areas of the center that effectively can alert the staff on duty of emergencies or patient needs;

(5) Access to an outside telephone line;

(6) Handrails in halls, stairwells, and bathrooms;

(7) Childproof electrical outlets in public areas;

(8) Access to a drinking fountain or potable drinking water with a disposable cup dispenser;

(9) A system to provide emergency lighting; and

(10) A separate area for storing clean and sterile supplies.

(D) Each center shall establish and maintain safety guidelines, practices, and policies which are reviewed at least once every twelve months to ensure a safe environment for patients, families, visitors and staff members. The center shall conduct and maintain records of the following:

(1) Evaluation of the heat, ventilation, emergency lighting, waste disposal, water supply, laundry, and kitchen equipment; and

(2) Evaluation of the physical environment for hazards that may cause injury from falls, electrical shock, poisoning, and burns. Risk factors of hazards include, but are not limited to, unsafe toys, unprotected stairs, and unlocked storage cabinets. The review of the physical environment shall include the exterior of the facility including walkways, parking lots, and outside recreation areas.

(E) Each center may provide laundry services on-site or off-site. Centers that provide laundry services on-site shall provide an area for laundry equipment with counter and storage space. The center shall provide for the separate collection, storage, and disposal of soiled materials. Soiled laundry shall be held in the soiled holding area until deposited in the washer.

(F) Sterile supplies may be prepackaged disposables or processed off-site. If the center sterilizes instruments and supplies on-site, an area for accommodation of sterilizing equipment in a a type and number sufficient and appropriate to the patient volume of the center shall be provided.

(G) Each center shall provide an area for families to store and serve light refreshments. The area shall include a sink, counter space, oven or microwave, refrigerator, cooking utensils, disposable tableware or dishwasher, storage space, and a seating area.

(H) Each center shall provide in each birth room, an area for equipment and supplies for newborn care and a separate area for the equipment and supplies for maternal care.

Last updated August 1, 2023 at 2:30 PM

Supplemental Information

Authorized By: 3702.13, 3702.30
Amplifies: 3702.12, 3702.13, 3702.30
Five Year Review Date: 7/15/2027
Prior Effective Dates: 1/13/1996