Skip to main content
Back To Top Top Back To Top
This website publishes administrative rules on their effective dates, as designated by the adopting state agencies, colleges, and universities.

Rule 4101:4-4-05 | Clearances.

 

When boilers are replaced or new boilers installed in either existing or new buildings, a minimum clear space of three feet shall be provided on the control and service sides of the boiler. All other sides shall comply with the boiler manufacturer's installation instructions for clearances to combustible materials. All boilers shall be so located that adequate space will be provided for the proper operation of the boiler and its appurtenances, for the inspection of all surfaces, tubes, water walls, economizer piping, valves, and other equipment, and for their necessary maintenance and repair.

Last updated March 20, 2024 at 12:59 PM

Supplemental Information

Authorized By: 4104.02(A)
Amplifies: 4104.02(A)
Five Year Review Date: 4/25/2024
Prior Effective Dates: 10/1/1966, 9/1/1994, 4/1/2000