The owner or operator shall conduct, at a minimum, the following monitoring and inspections when incinerating hazardous waste:

(A) Existing instruments which relate to combustion and emission control shall be monitored at least every fifteen minutes. Appropriate corrections to maintain steady state combustion conditions shall be made immediately either automatically or by the operator. Instruments which relate to combustion and emission control include those measuring waste feed, auxiliary fuel feed, air flow, incinerator temperature, scrubber flow, scrubber pH, and relevant level controls.

(B) The complete incinerator and associated equipment, including but not limited to, pumps, valves, conveyors, and pipes, shall be inspected at least daily for leaks, spills, and fugitive emissions, and all emergency shutdown controls and system alarms shall be checked to assure proper operation.