Section 3781.112 | Secured facility may use delayed egress and coded doors.

 
You are viewing a new version of this section that is not yet in effect View Current Version

(A) As used in this section, "secured facility" means any of the following:

(1) A maternity home licensed under Chapter 3711. of the Revised Code;

(2) A pediatric intensive care unit;

(3) A hospital licensed under Chapter 3722. of the Revised Code;

(4) A hospital licensed under section 5119.33 of the Revised Code to receive persons with mental illnesses;

(5) The portion of a nursing home licensed under section 3721.02 of the Revised Code or in accordance with section 3721.09 of the Revised Code in which specialized care is provided to residents of the nursing home who have physical or mental conditions that require a resident to be restricted in the resident's freedom of movement for the health and safety of the resident, the staff attending the resident, or the general public.

(B) A secured facility may take reasonable steps in accordance with rules the board of building standards adopts under division (A) of section 3781.10 of the Revised Code and in accordance with the state fire code the fire marshal adopts under section 3737.82 of the Revised Code, to deny egress to confine and protect patients or residents of the secured facility who are not capable of self-preservation. A secured facility that wishes to deny egress to those patients or residents may use delayed-egress doors and electronically coded doors to deny egress, on the condition that those doors are installed and used in accordance with rules the board of building standards adopts under division (A) of section 3781.10 of the Revised Code and in accordance with the state fire code the fire marshal adopts under section 3737.82 of the Revised Code. A secured facility also may install controlled-egress locks, in compliance with rules the board of building standards adopts under division (A) of section 3781.10 of the Revised Code and in compliance with the state fire code the fire marshal adopts under section 3737.82 of the Revised Code, in areas of the secured facility where patients or residents who have physical or mental conditions that would endanger the patients or residents, the staff attending the patients or residents, or the general public if those patients or residents are not restricted in their freedom of movement. A secured facility that uses delayed-egress doors and electronically coded doors, controlled-egress locks, or both, shall do both of the following:

(1) Provide continuous, twenty-four-hour custodial care to the patients or residents of the facility;

(2) Establish a system to evacuate patients or residents in the event of fire or other emergency.

The Legislative Service Commission presents the text of this section as a composite of the section as amended by multiple acts of the General Assembly. This presentation recognizes the principle stated in R.C. 1.52(B) that amendments are to be harmonized if reasonably capable of simultaneous operation.